This research project studies the role of pulse repetition rate in laser removal of black soiling crust from siliceous sandstone, and specifically, how laser fluence correlates with high pulse repetition rates in cleaning practice. The aim is to define practical cleaning processes and determine simple techniques for evaluation based on end-users’ perspective (restorers). Spot and surface tests were made using a Q-switched Nd:YAG laser system with a wide range of pulse repetition rates (5–200 Hz), systematically analysed and compared by macrophotography, portable microscope, stereomicroscope with 3D visualizing and area roughness measurements, SEM imaging and spectrophotometry. The results allow the conclusion that for operation under high pulse repetition rates the average of total energy applied per spot on a treated surface should be attendant upon fluence values in order to provide a systematic and accurate description of an actual laser cleaning intervention.
The development of laser cleaning from its beginnings, and mainly since the late 1990s, has led to its frequent use on several architectural heritage projects. The technique is referred to in general publications about stone conservation (
The literature provides essential information in order to set parameters on laser application. According to publications, the main parameters controlling the technique are wavelength, pulse duration (characteristics of the equipment which the restorer cannot normally modify), fluence or energy density, repetition rate and whether the treatment is performed in wet or dry conditions (parameters adjustable by the restorer). Most of the parameters described focus on fluence, often accompanied by technical data of laser equipment which restricts knowledge of planning, treatment performance and extrapolation of data for similar situations.
For this purpose it is fundamental to understand and consider all practical issues encountered in an actual laser cleaning intervention. In practice, upon laser cleaning, restorer directs laser beam manually onto the surface with a hand-held device. The cleaning is performed from the repeated incidence of laser beam on soiling deposits for a period of time determined by the restorer's observation in order to achieve the required cleaning level. In this process, dependent on several factors (material, soiling, equipment and application), either a satisfactory result can be reached or the substrate can be altered. Damage, if it occurs, is generally manifested as material loss and/or partial mineral fusion (related to photothermal and photomechanical mechanisms of the technique) and colour changes (related to migration of yellow polar crust compounds, chemical mineral alteration or uneven crust removal) (
These studies have been conducted with low pulse repetition rate equipment; however, laser systems of high repetition rate (200 Hz or higher) have recently been introduced into the conservation market and practice, and a systematic study of their cleaning procedure and use, in comparison to the usual low repetition ones (lower than 30 Hz), has not been established yet.
With both low and high repetition rate equipment, laser cleaning depends on the restorer's manually operated laser beam movement and on spot overlapping. It therefore seems necessary to study the spot as a starting point to understand the cleaning process.
Through different spot and surface tests, this paper studies how laser fluence correlates with high frequency rates and average of total energy applied per spot on the basis of existing practices. Results and conclusions are based on the experience and perspective of restorers. A proposal is made for an applied methodology to report previous tests and decisions during an actual intervention with these laser systems. It systematizes useful procedures for end-users and determines simple techniques for a preliminary evaluation highlighting potential surface alterations because they are easily interpretable by the restorer.
Tests were carried out on a column fragment from a late 19th century building in the Eixample, Barcelona, Spain. The fragment was located on the upper floor, approximately 20 m high, sheltered by a cornice at the SW façade. A preliminary study of the material (siliceous sandstone) and its alteration (black soiling crust) was conducted and the data obtained were used to direct the trials. Even though it is a studied stone material (
Spot and surface cleaning tests in dry conditions were made in laboratory simulating in situ treatment. The equipment used was a Q-switched Nd:YAG diode pumped laser at 1064 nm, pulse duration 5–10 ns, energy 2–12 mJ adjustable, repetition rate 5–200 Hz adjustable, average power 2.1 W, fibre transmitted, hand-held device and divergent focus optics. This equipment, unlike common laser systems, has a low pulse energy but higher repetition rate and it has been used in some studies (
Initially, to evaluate spot and surface tests, mainly crust removal and potential surface alteration, each sample was analysed by macrophotography and portable microscope (PCE-MM200 with ×10–200 adjustable), considered as in situ evaluation. Surface tests were also analysed by SEM. Subsequently, surface roughness and colour measurements were taken to evaluate cleaning tests (
Primary profile of spot and surface tests were evaluated by a Leica M165C stereomicroscope with software Leica Stereo-Explorer 3D visualizing and surface roughness measurements. Additionally, surface test images at ×20 were taken and mean values for the area field roughness parameters (
As an indicator of cleaning degree, CIELab measurements were conducted before and after treatment with a spectrophotometer (Konica Minolta CM-2600d). Three measurements were taken of each soiled and cleaned surface test using a target mask of Ø3 mm, specular component included, illuminant D65 and 10° observer. The total colour change ΔE* was calculated according to CIELab 1976 [ΔE*=(ΔL*2+Δa*2+Δb*2)1/2]. Because of colour in rock fracture would be an excessive cleaning, the reference value for evaluation was taken from comparison between test.
These analytical techniques present data easily interpretable by the restorer, providing useful information to distinguish cleaning effects on stone surface and to take decisions in an actual intervention.
The stone is Montjuïc siliceous sandstone, a commonly used building material in Barcelona throughout its history. The column fragment corresponds to the grey lithology. This is a variety with a high content of quartz (80–90% volume), slight amount of feldspar and mica (<10% volume), minor degree of rock fragments (schist, quartzite, etc.; ≤0.5–2% volume) and porosity between 18–20%. Mineral grains are equigranular with subangular forms (ranging from 150 to 300 µm), cement is siliceous and texture relatively homogeneous, quite compact. Surface finishing is smooth (honed finishing), being understood in this case as microrough due to the grain size.
Stone surface was well preserved although it had a black soiling crust ranging from 85 to 180 µm. The crust does not seem to affect the substrate petrographic texture at any place (
Cross section: stone and crust SEM-BSE image (left) and stone and crust stereomicroscope image (right). Scale 200 µm.
The most influential of these properties on laser cleaning are mineralogical composition, colour, porosity and texture. Colour difference between soiling (black) and stone (light-grey) seems to make treatment feasible. Porosity, texture and surface finishing could make the cleaning process more difficult increasing the possibility of substrate laser absorption. Some material loss and/or colour changes could be provoked owing to sandstone mineralogical composition (
At the outset, it was decided to follow the standard (
Analysing technical characteristics of the equipment used, it was decided to adapt the standard to the specific situation because design and settings of this laser system are different from the common equipment. The spot diameter will always be smaller because its focal distance, approximately 3 cm, generates spots ranging from 1 to 1.5 mm2. Due to defocusing, it does not allow a significant increase/decrease of spot area without considerable loss of effectiveness and otherwise the variation of energy density leads to non-homogeneous results as in similar systems (
In addition, mainly due to high repetition rate, consideration was also given to which defining parameter, besides fluence, would be used to define the treatment, particularly for surface tests. Owing to restorer's manually operated laser beam movement and to its overlapping during laser cleaning practice, it could be considered that numerical value of fluence may appear incomplete because it does not include spot movement during cleaning.
Fluence (F) relates energy and area and expresses laser/matter interaction as pulse energy applied in a given area [F = E/A; expressed in J/cm2] (
In this case, some authors (
From this theoretical approach and to establish comparatives, spot and surface tests in dry conditions were made keeping energy, time, distance and angle constant, only modifying repetition rate (in the available range of 5 to 200 Hz). Energy was set at 10 mJ because previous tests with this equipment in similar situations have shown that lower energies have no cleaning effect or rather are cost-effectively unviable in an actual intervention (
Three spot tests (referred to as A, B, C) with each available repetition rate were carried out in dry conditions keeping energy, time, distance and angle constant and laser beam was guided directly onto the sample. In addition to fluence, repetition rate and time interval are reflected in the average of total energy per spot.
Surface tests in dry conditions were performed on small contiguous surfaces of 0.27 cm2 (0.9×0.3 cm) to reduce potential differences in bonding between crust/substrate and to include restorer's manual movement of laser beam without changes in distance and angle that could influence the results. Energy, distance and angle remained the same as in spot tests only modifying the available repetition rate. A reference rail was used to maintain distance and angle.
A fixed time interval was not set in order to allow the restorer to adjust the number of pulses according to characteristics of treated area. As the intention was to reproduce an actual cleaning, irradiation time can differ depending on immediate visual assessment and on the selected repetition rate. Treatment time for each surface test was recorded.
To provide reference of the initial situation, and related with an actual cleaning, surface tests were masked and every cleaned surface was covered after treatment in order to prevent visual comparisons that could influence the restorer, especially in treatment time.
Consequently, in this case, as well as fluence and repetition rate, the amount of cleaned area and irradiation time must also be taken into account (reflected in average of total energy per spot calculation).
Fluence indicates that results do not reflect pulse repetition rate and that the average of total energy per spot is clearly related to repetition rate and treatment time (
Spot tests parameters and results
Spot test | Constant parameters | Variable parameters | ||||||
---|---|---|---|---|---|---|---|---|
Energy (mJ) | Spot (cm2) | Fluence (J/cm2) | Time (s) | Repetition rate (Hz) | Eavg spot (J) | Results | ||
PL-M1 | A | 10 | 0.0113 | 0.8849 | 10 | 5 | 0.50 | D |
B | D | |||||||
C | ND | |||||||
PL-M2 | A | 10 | 0.0113 | 0.8849 | 10 | 10 | 1 | D |
B | D | |||||||
C | ND | |||||||
PL-M3 | A | 10 | 0.0113 | 0.8849 | 10 | 50 | 5 | D |
B | ND | |||||||
C | D | |||||||
PL-M4 | A | 10 | 0.0113 | 0.8849 | 10 | 100 | 10 | ND |
B | D | |||||||
C | ND | |||||||
PL-M5 | A | 10 | 0.0113 | 0.8849 | 10 | 150 | 15 | ND |
B | ND | |||||||
C | D | |||||||
PL-M6 | A | 10 | 0.0113 | 0.8849 | 10 | 200 | 20 | D |
B | D | |||||||
C | ND |
Legend: (ND) no damage, (D) material loss.
Spot analysis using portable microscope and 3D stereomicroscope with visualizing and surface roughness measurements show that morphologically the treated area in some cases is uneven (
Spots (theoretical circumference in dotted circle) and spots surface topography: irregular spot shape and uneven spot cleaning (left) and regular spot shape (top right). Topography in uniform texture: theoretical spot (in red circle), depression by material loss in treated area —A— and similar depression in the untreated one —B— (bottom right). 3D stereomicroscope images. Scale 300 µm.
To confirm these deviations, theoretical circumference of spot test was superimposed on the images. It can be observed that laser beam disperses on the surface in some cases and the cleaning effect outside the theoretical spot, if it occurs, is less intense. As absorption capacity also depends on surface irregularities, the uneven microrough stone texture has a larger specific area and the reflected laser beam may have different interactions with minerals. Therefore the total area can absorb more energy on average (
In all spot tests a central area with a more intense cleaning effect (or damage) can occasionally be seen. Image analysis shows that if damage occurs, it corresponds with a very defined circular spot where energy density could have been more concentrated due to beam reflection depending on mineral grain orientation (
Regular spot shape with punctual material loss (left). Primary profile of analysed area with spot area in dotted rectangle: similar peaks and valleys in treated area and in the untreated one (right). 3D stereomicroscope image. Scale 300 µm.
Primary profile analysis failed to provide sufficient information for evaluation. Crust is removed but primary profiles do not clearly reflect it because the stone microroughness has similar, or even lower, peaks and valleys to those of the untreated area (
Fluence is the same as in spot tests because energy, distance and hence spot area were constant. However, the average of total energy per spot is different because it depends on repetition rate and restorer's manual laser beam movement during cleaning (reflected in treatment time). Differential value is the average of total energy per spot calculated from the number of pulses necessary to achieve soiling ablation in a specific area and time. It can be seen that the higher the pulse repetition rate, the more the average of pulses per spot increases because restorer is unable to move the hand-held device at the rate which the laser emits, considered by some authors a waste of energy (
Surface tests parameters and results
Surface test | Constant parameters | Variable parameters | ||||||
---|---|---|---|---|---|---|---|---|
Energy (mJ) | Spot (cm2) | Fluence (J/cm2) | Area (cm2) | Repetition rate (Hz) | Time (s) | Eavg spot (J) | Results | |
PLS1-M1 | 10 | 0.0113 | 0.8849 | 0.27 | 5 | 17 | 0.0356 | D |
PLS1-M2 | 10 | 11 | 0.0460 | ND | ||||
PLS1-M3 | 50 | 6 | 0.1256 | ND | ||||
PLS1-M4 | 100 | 6 | 0.2511 | ND | ||||
PLS1-M5 | 150 | 5 | 0.3139 | ND | ||||
PLS1-M6 | 200 | 7 | 0.5859 | D |
Legend: (ND) no damage, (D) material loss.
Analysing surfaces by macrophotography, portable microscope and stereomicroscope, punctual spot irradiation or beam movement marks on the treated surface cannot be distinguished. Dynamic parameter of spot movement seems to unify cleaning because the restorer adapts it by immediate visual assessment, reducing laser beam/substrate interaction. However, some material loss in sandstone binding phases and a slightly dark shade on some specks are observed in PLS1-M1 (at 5 Hz) and PLS1-M6 (at 200 Hz) in comparison with other trials (
Macrophotography of surface tests at different repetition rate. Scale 3 mm (top). Surface tests (inset with theoretical spot area): punctual dark shading in dotted area and material loss in red circle. 3D stereomicroscope image. Scale 1.5 mm (centre). Cross section: punctual dark shading linked to crust residues after cleaning. 3D stereomicroscope image. Scale 150 µm (bottom).
Area roughness analysis indicates no significant difference in any test (
Area roughness analysis of soiled surface —SS— and of surface tests: Sa-Sq (A) and S10z (B) parameters, volume parameters (C) and ratio Vvc/Vmc (D).
Taking into account volume parameters it can be ascertained that Vmp and Vvv are similar in all surface tests suggesting that peaks and valleys remain relatively unchanged. Analysing the core volume, both Vmc and Vvc have a similar behaviour to Sa and Sq. Nevertheless Vvc/Vmc ratio seems to describe more likely surface behaviour indicating that PLS1-M1 and PLS1-M6 have a higher volume void, suggesting a higher degree of cleaning (or damage).
Analysing surface tests colour, cleaning leads to colour changes in all surface tests in comparison to soiled surfaces. However, although the increase in lightness (ΔL*) is noticeable with the naked eye, it is more evident in PLSM-2, PLSM-3, PLSM-4 and PLSM-5. Changes in Δa* and Δb* are limited but more significant in the same surface tests. The total colour change (ΔE*) between cleaned and soiled surfaces indicate that PLSM-1 and PLSM-6 are the least cleaned surface tests (
Colour analysis of surface tests: ΔL*, Δa*, Δb* coordinates (A) and ΔE* (B).
Area roughness (mainly volume parameters) and colour analysis show that results are similar to those obtained by optical techniques: PLSM-1 and PLSM-6 have the highest volume void (related to some material loss) and are the least cleaned surface tests.
Material loss, as in spot tests, is usually related to sandstone binding phases. According to most references on siliceous sandstones (
Some studies have documented darkening of quarry and monument specimens of siliceous sandstones (
To explain this dark shading significant differences in bonding between crust/substrate are also discarded due to the reduced size of total test area. Although it is complex to determine, this occasional dark shading seems related to restorer's laser beam movement and its visual assessment during cleaning which can leave some specks treated in a different way than other surface tests. Some restorers refer to a dot effect during laser cleaning (
SEM-BSE image of PLS1-M5 and PLS1-M6 —(U) untreatred, (T) treated—. Punctual dark shading similar to black soiling crust in red dotted area. Scale 200 µm.
According to the results, using the same fluence in an actual cleaning with high repetition rate equipment the restorer would be able to select the lowest averages of total energy applied per spot that have not caused damage from previous surface tests (in this case between 0.046–0.313 J), selecting the cleaning level after colorimetric measurements. As a result, if some soiling residues remained on the surface due to restorer's fast beam movement, he could leave a more homogeneous surface supplying supplementary pulses at these specific points.
From the results, it can be observed that for operation under high pulse repetition rates the average of total energy per spot could be a useful parameter and should be attendant upon fluence for a systematic and accurate description of a cleaning intervention by the restorer. In addition to fluence, average of total energy per spot in an actual cleaning allows for taking into account the required manual laser beam movement, especially when high repetition rate equipment is used.
Prior to an actual cleaning intervention, spot analysis provides useful information about cleaning effects and potential surface damage on a specific small area. To clarify cleaning practice it is subsequently necessary to corroborate the data obtained through surface tests, including restorer's manual spot movement, to determine practical issues.
Simple techniques allowing comparative optical evaluation at different scales provide useful information for a preliminary spot and surface test analysis following the needs of restorers in an actual intervention. Direct observation and images obtained clarify preliminary interpretation because surface deposits are essentially perceived as a modification of visual parameters of what is considered a soiled or clean surface. SEM images, area roughness and colour analysis add further accurate information for cleaning assessment with data easily interpretable by the restorer. Comparative analysis with these techniques could be appropriate to control and monitor cleaning effectiveness in an actual intervention. The correlation of data obtained from each of these techniques adds significant information to the evaluation of effects on treated surface morphology.
To Dr. Salvador Borrós and María José Alcayde Palanca (GEMAT, Institut Químic de Sarrià, Universitat Ramon Llull) for facilitating the use of 3D stereomicroscope. To Núria Guasch Ferré (GRAPAC/CETEC-patrimoni, Universitat Autònoma de Barcelona) for their suggestions.